GUID-FA37DCA8-623A-4AFE-943F-F9E2968B7080 V1 EN
Figure 37: Limit value supervision
Table 26: Settings for RTD/mA input limit value supervision
Function
Settings for limit value supervision
RTD/mA input Out of range Value maximum
High-high limit Val high-high limit
High limit Val high limit
Low limit Val low limit
Low-low limit Val low-low limit
Out of range Value minimum
When the measured value exceeds either the Value maximum parameter or the Value
minimum parameter, the corresponding quality is set to “Out of range”.
6.1.4.6 Deadband supervision
Deadband settings are used to select how sensitively RIO600 sends the updated
measurements to data subscriber over the GOOSE and Modbus communication. The
deadband settings must be sensitive enough to report events fast enough but also
insensitive enough not to load the Ethernet network with unnecessary events.
The deadband functionality decides the percentage change in the input values that
needs to be reported to the application. If the percentage change between the current
measured values and the last reported values is greater than the set DeadBand Value
(in %) of the measured range, the current measurement is reported to the application.
Section 6 1MRS757488 H
Commissioning
66 RIO600
Installation and Commissioning Manual