6.1.6 Operating parameter settings of SIM8F module
Table 28: Operating parameter settings of SIM8F module
Parameter name
Range Unit Step Default Description
Frequency 50
60
Hz - 50 Hz Rated system
frequency
Nominal current 80…630 A 1 400 Nominal phase
current
Nominal voltage 500…48000 V 1 15000 Nominal phase-
to-phase voltage
Rated sensor current 80
250
A - 80 Rated primary
current of sensor
Io signal sel Calculated Io
Measured Io
- - Calculated Io Selection used
for Io signal
Phase Rotation ABC
ACB
- - ABC Phase rotation
order
Sensor Correction Factors
Phase A Current
Amplitude
0.7000…1.3000 - 0.0001 1.0000 Amplitude
correction factor
for current
sensor, phase A
Current Phase
-3.0000…
+3.0000
deg 0.00025 0.000 Phase correction
factor for current
sensor, phase A
Voltage
Amplitude
0.7000…1.3000 - 0.0001 1.0000 Amplitude
correction factor
for voltage
sensor, phase A
Voltage Phase
-3.0000…
+3.0000
deg 0.00025 0.000 Phase correction
factor for voltage
sensor, phase A
Phase B
Current
Amplitude
0.7000…1.3000 - 0.0001 1.0000 Amplitude
correction factor
for current
sensor, phase B
Current Phase
-3.0000…
+3.0000
deg 0.00025 0.000 Phase correction
factor for current
sensor, phase B
Voltage
Amplitude
0.7000…1.3000 - 0.0001 1.0000 Amplitude
correction factor
for voltage
sensor, phase B
Voltage Phase
-3.0000…
+3.0000
deg 0.00025 0.000 Phase correction
factor for voltage
sensor, phase B
Table continues on next page
1MRS757488 H Section 6
Commissioning
RIO600 69
Installation and Commissioning Manual