Parameter name Range Unit Step Default Description
Fault Indication Reset Method Self Reset
Method,
Definite Time,
Voltage
Presence,
DT or Voltage
Presence
-
- Definite Time Self Reset
Method: Flashing
protection
indication LED is
reset
immediately
once the fault is
cleared.
Definite Time:
Flashing
protection
indication LED is
reset after the
definite time set
by LED reset
time delay.
Voltage
Presence:
Flashing
protection
indication LED is
reset after the
presence of 3 ph
voltage.
DT or Voltage
Presence: ORing
of above two
methods.
Update Interval for Metering Values
1...15 - 1 4 Update interval
for metering
values × 500 ms
New installation
- - - - Performs reset of
energy counter
and internal
statistics
information
Rated Sensor Current set as 80 A refers to 150 mV at 50 Hz and 180
mV at 60 Hz when 80 A is injected. Similarly, Rated sensor current
set as 250 A refers to 150 mV at 50 Hz and 180 mV at 60 Hz when 250
A is injected.
6.1.6.1 Functions available in SIM8F
Table 29: Functions available in SIM8F
Function
IEC 61850 IEC 60617 IEC-ANSI
Edition 1 Edition 2
Measurement functions
Three-phase current
measurement
CMMXU CMMXU 3I 3I
Three-phase voltage
measurement
VMMXU VMMXU 3U 3U
Residual current measurement RESCMMXU RESCMMXU Io Io
Table continues on next page
1MRS757488 H Section 6
Commissioning
RIO600 71
Installation and Commissioning Manual