Parameter name Range Unit Step Default Description
Phase C Current
Amplitude
0.7000…1.3000 - 0.0001 1.0000 Amplitude
correction factor
for current
sensor, phase C
Current Phase
-3.0000…
+3.0000
deg 0.00025 0.000 Phase correction
factor for current
sensor, phase C
Voltage
Amplitude
0.7000…1.3000 - 0.0001 1.0000 Amplitude
correction factor
for voltage
sensor, phase C
Voltage Phase
-3.0000…
+3.0000
deg 0.00025 0.000 Phase correction
factor for voltage
sensor, phase C
Residual
Current
Amplitude
0.7000…1.3000 - 0.0001 1.0000 Amplitude
correction factor
for current
sensor, residual
Current Phase
-3.0000…
+3.0000
deg 0.00025 0.000 Phase correction
factor for current
sensor, residual
LED Reset Time Delay
1…1440 min 1 60 LEDs Reset
delay time
(incase no
external signal
received for
resetting). This is
applicable to
THD/TDD, OC
and EF fault
indication LEDs.
Default Load Flow Direction Forward,
Reverse
- - Forward Load flow
direction
selection. The
load flow
direction LED
color for Forward
selection is,
Forward =
Green, Reverse
= Red and vice
versa.
THD & TDD LED colors THD = Red, TDD
= Green
THD = Green,
TDD = Red
-
- THD = Green
TDD = Red
THD & TDD LED
indication
Protection LED Colors Forward = Red,
Reverse = Green
Forward =
Green, Reverse
= Red
-
- Forward = Green
Reverse = Red
Over Current
Direction LED
indication
Common setting
for DOC and
DEF
Table continues on next page
Section 6 1MRS757488 H
Commissioning
70 RIO600
Installation and Commissioning Manual