Table 169: SCM application types
Reg A Type IEC 61850 name SA name Description Values
SCM
1500 i16 Application Type (Application type –
Value)
4I4O – 128;
Three position
switch – 129;
Two position
disconnector – 130;
Two position earth –
131;
Circuit breaker –
132;
1501 i16 Application Type
1502 i16 Application Type
1503 i16 Application Type
1504 i16 Application Type
1505 i16 Application Type
1506 i16 Application Type
1507 i16 Application Type
1508 i16 Application Type
1509 i16 Application Type
7.2.44 Binary readable signals of SCM
Table 170: Binary readable signals of SCM
Bit A
Reg A IEC 61850 name SA name Description Values
1)
1. LD0.SCMLGGIO1/
LD0.SCMHGGIO1
2. LD0.SCMLPGGIO1/
LD0.SCMHPGGIO1
3. LD0.SCMLDGGIO1/
LD0.SCMHDGGIO1
4. LD0.SCMLEGGIO1/
LD0.SCMHEGGIO1
5. LD0.SCMLCGGIO1/
LD0.SCMHCGGIO1
6. LD0.TCSLSCBR1/
LD0.TCSHSCBR1
SCM-1
1664 1516 .Ind1.stVal Digital Input Channel 1 0/1 = Off/On
1665 1516.01 .Ind2.stVal Digital Input Channel 2 0/1 = Off/On
1666 1516.02 .Ind3.stVal Digital Input Channel 3 0/1 = Off/On
1667 1516.03 .Ind4.stVal Digital Input Channel 4 0/1 = Off/On
1668 1516.04 RELEASE_ES Release Earth Switch
Information
0/1 = Off/On
1669 1516.05 RELEASE_DS Release Disconnector
Information
0/1 = Off/On
1670 1516.06 REED_ES REED Earth Switch
Information
0/1 = Off/On
1671 1516.07 RELEASE_CB Release Circuit Breaker
Information
0/1 = Off/On
1672 1516.08 .Ind10.stVal Error Code: No Fault 0/1 = Off/On
1673 1516.09 .Ind11.stVal Error Code: Device Error 0/1 = Off/On
1674 1516.1 .Ind12.stVal Error code: Release 0/1 = Off/On
Table continues on next page
Section 7 1MRS757488 H
Modbus TCP communication
242 RIO600