Section 6 Commissioning
6.1 Parameter setting
The operating parameters of the LECM, DIM8H, DIM8L,DOM4, RTD4, AOM4,
SIM8F and SIM4F modules.
6.1.1 Operating parameter settings LECM
Table 20: Operating parameter settings for LECM
Parameter name Range Unit Default value Description
General Parameters
Test Mode Disable/Enable Disable This parameter enables or disables the
Test
mode
parameter in RIO600.
Standalone configuration False/True False If enabled, RIO600 operates in standalone mode
without any GOOSE/Modbus commands
Communication
IP Address 192.168.2.10 IP address for RIO600
Subnet Mask 255.255.255.0 Subnet mask address for RIO600
Default Gateway 192.168.2.1 Gateway address for RIO600
Synch Source None/SNTP/Modbus None Time synchronization (SNTP) selection.
None: SNTP functionality not selected. If the
SNTP time synchronization is not required or
available, the
Synch Source
parameter must be
set to “None". RIO600 displays the default time on
the WHMI in red to indicate that time is not
synchronized.
SNTP: SNTP functionality selected. If two
separate SNTP servers are available, their IP
addresses can be configured with parameters
IP
SNTP Primary
and
IP SNTP Secondary
. If a
single SNTP server is used, its IP address can be
configured in the
IP SNTP Primary
parameter,
and the
IP SNTP Secondary
parameter can be
configured as "0.0.0.0".
Modbus: Syncronization by unsigned 16 bit UTC
time.
IP SNTP Primary 10.58.125.165 IP address for SNTP server 1
Table continues on next page
1MRS757488 H Section 6
Commissioning
RIO600 57
Installation and Commissioning Manual