7.2.15 LD0.DEFPTOC directional earth-fault detection
Table 140: LD0.DEFPTOC directional earth-fault detection
Bit A
Reg A IEC 61850 name SA name Description Values
LD0.DEFPTOC1 SIM8F-1
536 385.08 .Str.general START General Start 1 = Start
537 385.09 .Op.general Operate General Operate 1 = Operate
540 385.12 .OpFwd.general Forward Operate 1 = Operate
541 385.13 .OpRev.general Reverse Operate 1 = Operate
LD0.DEFPTOC2 SIM8F-2
568 387.08 .Str.general START General Start 1 = Start
569 387.09 .Op.general Operate General Operate 1 = Operate
572 387.12 .OpFwd.general Forward Operate 1 = Operate
573 387.13 .OpRev.general Reverse Operate 1 = Operate
LD0.DEFPTOC3 SIM8F-3
664 801.08 .Str.general START General Start 1 = Start
665 801.09 .Op.general Operate General Operate 1 = Operate
668 801.12 .OpFwd.general Forward Operate 1 = Operate
669 801.13 .OpRev.general Reverse Operate 1 = Operate
LD0.DEFPTOC4 SIM8F-4
696 803.08 .Str.general START General Start 1 = Start
697 803.09 .Op.general Operate General Operate 1 = Operate
700 803.12 .OpFwd.general Forward Operate 1 = Operate
701 803.13 .OpRev.general Reverse Operate 1 = Operate
LD0.DEFPTOC5 SIM8F-5
728 805.08 .Str.general START General Start 1 = Start
729 805.09 .Op.general Operate General Operate 1 = Operate
732 805.12 .OpFwd.general Forward Operate 1 = Operate
733 805.13 .OpRev.general Reverse Operate 1 = Operate
7.2.16 LD0.MFAPSDE multifrequency admittance protection
(earth-fault indication)
Table 141: LD0.MFAPSDE multifrequency admittance protection
Bit A
Reg A IEC 61850 name SA name Description Values
LD0.MFAPSDE1 SIM8F-1
736 806 .Str.general Start General Start 1 = Start
737 806.01 .Op.general Operate General Operate 1 = Operate
738 806.02 .RevEF.stVal Reverse Earth Fault 1 = Fault
Table continues on next page
Section 7 1MRS757488 H
Modbus TCP communication
212 RIO600
Installation and Commissioning Manual