Settings
Table 79: MFAPSDE Settings
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
Power direction logic Disable
Enable
- - Enable Power direction logic
Peak Counter Limit 3...20 - - 3 Peak counter limit
for intermittent
(restriking) EF
detection
Operating Quantity
Adaptive
Amplitude
Resistive
-
- Adaptive Operating quantity
selection
Voltage Start Value 500...10000 V 1 500 Voltage start value
Operate Delay Time 60...60000 ms 1 500 Operate delay time
Directional Mode Forward
Reverse
- - Forward Directional mode
Tilt Angle 5...20 Deg 1 10 Characteristics tilt
angle
Reset Delay Time 0...60000 ms 1 500 Reset delay time
Start Delay Time 30...60000 ms 1 30 Start delay time
Min Forward
Operate Current
1.0...20.0 A 0.1 1 Minimum operate
current in forward
direction
Min Reverse
Operate Current
1.0...20.0 A 0.1 1 Minimum operate
current in reverse
direction
Table 80: MFAPSDE Technical data
Characteristic
Value
Operation accuracy At frequency f = f
n
±5% in the range of 480 V...9.6 kV
±0.5% in the range of 9.6...28.8 kV
Operate time accuracy
±1.0% of the set value or ±20 mS
6.1.6.6 Voltage presence indication
Voltage presence indication PHSVPR
Identification
Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage presence indication PHSVPR PHSVPR PHSVPR
1MRS757488 H Section 6
Commissioning
RIO600 135
Installation and Commissioning Manual