The binary input is regarded as non-oscillating if the number of valid state changes
during configured time period is less than the set oscillation level value minus the set
oscillation hysteresis value. The oscillation hysteresis must be set lower than the
oscillation level to enable the input to be restored from oscillation. When the input
returns to a non-oscillating state, the binary input is deblocked (the status is valid) and
an event is generated.
6.1.3 Operating parameter settings DOM4
Table 22: Operating parameter settings for DOM4
Parameter name Range Unit Default value Description
Description Digital Output
1...4
User defined channel name not exceeding 30
characters
Pulse Length 10 to 65535 ms 10 The integer value in this parameter indicates the
pulse length for the output channels in
milliseconds (ms). This parameter is configurable
separately for each output channel.
Signal Type
Static/Pulse Static output signal type: static/pulse
This parameter is configurable separately for
each output channel.
Output Channel 1
Inversion
Non-Inverted/Inverted Non Inverted channel 1 output type: non-inverted/inverted
Output Channel 2
Inversion
Non-Inverted/Inverted Non Inverted channel 2 output type: non-inverted/inverted
Output Channel 3
Inversion
Non-Inverted/Inverted Non Inverted channel 3 output type: non-inverted/inverted
Output Channel 4
Inversion
Non-Inverted/Inverted Non Inverted channel 4 output type: non-inverted/inverted
Output Channel 1
Enabled
Enabled/Disabled Enabled channel 1: enabled/disabled
Output Channel 2
Enabled
Enabled/Disabled Enabled channel 2: enabled/disabled
Output Channel 3
Enabled
Enabled/Disabled Enabled channel 3: enabled/disabled
Output Channel 4
Enabled
Enabled/Disabled Enabled channel 4: enabled/disabled
Table 23: Details of output channels on a DOM4 board configured for IRF
Status
Contact condition LED status
Power-on Open OFF
Normal operating condition Closed ON
IRF condition Open OFF
It is possible to map IRF condition to any binary output via Signal
Matrix in PCM600.