7.2.25 LD0.PHPTOC phase overcurrent fault detection
Table 150: LD0.PHPTOC phase overcurrent fault detection
Reg A
Type Scale IEC 61850 name SA name Description Values
LD0.PHPTOC1 SIM8F-1/SIM4F-1 0 = unknown
1 = forward
2 = reverse
3 = both
404
u16 1 .Str.dirgeneral General Start
405 u16 1 .Str.dirphsA Phase A Start
406 u16 1 .Str.dirphsB Phase B Start
407 u16 1 .Str.dirphsC Phase C Start
LD0.PHPTOC2 SIM8F-2/SIM4F-2
536 u16 1 .Str.dirgeneral General Start
537 u16 1 .Str.dirphsA Phase A Start
538 u16 1 .Str.dirphsB Phase B Start
539 u16 1 .Str.dirphsC Phase C Start
LD0.PHPTOC3 SIM8F-3/SIM4F-3
868 u16 1 .Str.dirgeneral General Start
869 u16 1 .Str.dirphsA Phase A Start
870 u16 1 .Str.dirphsB Phase B Start
871 u16 1 .Str.dirphsC Phase C Start
LD0.PHPTOC4 SIM8F-4/SIM4F-4
1000 u16 1 .Str.dirgeneral General Start
1001 u16 1 .Str.dirphsA Phase A Start
1002 u16 1 .Str.dirphsB Phase B Start
1003 u16 1 .Str.dirphsC Phase C Start
LD0.PHPTOC5 SIM8F-5/SIM4F-5
1132 u16 1 .Str.dirgeneral General Start
1133 u16 1 .Str.dirphsA Phase A Start
1134 u16 1 .Str.dirphsB Phase B Start
1135 u16 1 .Str.dirphsC Phase C Start
1MRS757488 H Section 7
Modbus TCP communication
RIO600 219