oscillation level to enable the input to be restored from oscillation. When the input
returns to a non-oscillating state, the binary input is deblocked (the status is valid) and
an event is generated.
6.1.8.3 Generic four inputs and four high speed power outputs
Smart control module has four inputs with common return for a pair and four power
outputs with common return for a pair. These channels can be used for generic
purposes, for example, position indications or status information.
Table 107: Operation parameters for generic inputs and high-speed power outputs
Parameter name Range Unit Default value Description
Input channels
Debounce Time (Filter
time)
5...4095 ms 10 This parameter is the
debounce time for the
input signal in ms.
Oscillation upper limit
2...63 Counts 63 This parameter is the
oscillation suppression
upper limit.
The parameter value acts
as the count for upper
limit.
Oscillation suppression
hysteresis
1...62 Counts 62 This parameter is the
oscillation suppression
hysteresis.
The parameter value acts
as the count for
hysteresis.
Oscillation time
0...4095 ms 4095 This parameter is the
oscillation suppression
time limit. The parameter
value acts as the time
window for the oscillation
detection in ms.
0 means that no
oscillation suppression is
active.
Description Digital input 1...4 User defined channel
name not exceeding 30
characters.
Channel 1 Inversion
Non-inverted/inverted Non-inverted Channel 1 input type:
non-inverted/inverted
Channel 2 Inversion Non-inverted/inverted Non-inverted Channel 2 input type:
non-inverted/inverted
Channel 3 Inversion Non-inverted/inverted Non-inverted Channel 3 input type:
non-inverted/inverted
Channel 4 Inversion Non-inverted/inverted Non-inverted Channel 4 input type:
non-inverted/inverted
Output channels
Description High speed output 1..4 User defined channel
name not exceeding 30
characters.
Table continues on next page
Section 6 1MRS757488 H
Commissioning
164 RIO600
Installation and Commissioning Manual

Table of Contents