7.2.4 Module identification
RIO600 modules can be identified with following register addresses. This
information can be useful to identify the information about modules connected on the
stack.
Table 129: Module identification
Reg A Type Scale IEC 61850 name SA name Description
Values
1)
16 u16 1 LECM Module Identification DOM = 66
DIM8 = 67
RTD = 68
AOM = 69
SIM8F = 70
SIM4F = 72
SCM = 71
LECM = 76
17 u16 1 Module 1 Identification
18 u16 1 Module 2 Identification
19 u16 1 Module 3 Identification
20 u16 1 Module 4 Identification
21 u16 1 Module 5 Identification
22 u16 1 Module 6 Identification
23 u16 1 Module 7 Identification
24 u16 1 Module 8 Identification
25 u16 1 Module 9 Identification
26 u16 1 Module 10 Identification
1) Modbus master can be informed about the RIO600 stack configuration by polling for the addresses corresponding to the module
identification address range
7.2.5 LD0.DIM8GGIO/LD0.DIM8LGGIO physical I/O states
Status of binary input information can be accessed using the following addresses of
DIM8H/DIM8L module.
Table 130: LD0.DIM8GGIO/LD0.DIM8LGGIO physical I/O states
Bit A
Reg A IEC 61850 name SA name Description Values
LD0.DIM8GGIO1/
LD0.DIM8LGGIO1
0 32.00 .Ind1.stVal DIM8H 1-Input 1 State 0/1=Off/On
1 32.01 .Ind2.stVal DIM8H 1-Input 2 State 0/1=Off/On
2 32.02 .Ind3.stVal DIM8H 1-Input 3 State 0/1=Off/On
3 32.03 .Ind4.stVal DIM8H 1-Input 4 State 0/1=Off/On
4 32.04 .Ind5.stVal DIM8H 1-Input 5 State 0/1=Off/On
5 32.05 .Ind6.stVal DIM8H 1-Input 6 State 0/1=Off/On
6 32.06 .Ind7.stVal DIM8H 1-Input 7 State 0/1=Off/On
7 32.07 .Ind8.stVal DIM8H 1-Input 8 State 0/1=Off/On
8 32.08 <reserved> <reserved> 0=Off
9 32.09 <reserved> <reserved> 0=Off
10 32.1 <reserved> <reserved> 0=Off
Table continues on next page
Section 7 1MRS757488 H
Modbus TCP communication