Rated Sensor Current set as 80 A refers to 150 mV at 50 Hz and 180
mV at 60 Hz when 80 A is injected. Similarly, Rated sensor current
set as 250 A refers to 150 mV at 50 Hz and 180 mV at 60 Hz when 250
A is injected.
6.1.7.1 Functions available in SIM4F
Table 98: Functions available in SIM4F
Function IEC 61850 IEC 60617 IEC-ANSI
Edition 1 Edition 2
Measurement functions
Three-phase current
measurement
CMMXU CMMXU 3I 3I
Residual current measurement RESCMMXU RESCMMXU Io Io
Current average and peak
measurement
CMSTA CAVMMXU
CMAMMXU
RCAVMMXU
-
-
Detection and indication functions
Three-phase non-directional
overcurrent fault detection
PHPTOC PHPTOC 3I> 51P
Non-directional earth-fault
detection
EFPTOC EFPTOC I0> 51N
Negative-sequence overcurrent
protection
NSPTOC NSPTOC I2> 46
Three-phase inrush detector INRPHAR INRPHAR 3I2f> 68
Fault passage indicator FPIPTOC FPIPTOC - -
6.1.7.2 Measurement functions
Three-phase current measurement CMMXU
See Measurement functions.
Residual current measurement RESCMMXU
See Measurement functions.
Current peak measurement CMSTA
See Measurement functions.
6.1.7.3 Three-phase current fault detection
Three-phase non-directional overcurrent fault detection PHPTOC
See
Three-phase non-directional overcurrent fault detection PHPTOC.
1MRS757488 H Section 6
Commissioning
RIO600 149
Installation and Commissioning Manual