5.2.8 Connecting SIM4F sensor signals
In RIO600, SIM4F accepts three phase current signals to RJ-45 connectors.
The input signals are fed from a current sensor based on the Rogowski coil principle.
The sensor should be equipped with an RJ-45 connector for connection with the
SIM4F module. There are current sensors which are wired to a single RJ-45 connector
with adapter.
Use the cable connector type RJ-45 for connecting the sensors with SIM4F.
Connect current signals to the sensor input for proper operation.
Preferred ABB current sensor is KECA 80 C85.
RIO600 supports also split-core current sensor type for retro-fit purposes. Preferred
split-core sensor is KECA 80 D85.
KEVCY XX RE1 RIO600
RJ-45
Cable RJ-45
GUID-3FE5111C-6DB7-4836-A187-CD4C363DB8C7 V1 EN
Figure 25: Connecting split-core current sensor to RIO600 RJ-45
Section 5 1MRS757488 H
Installing
46 RIO600
Installation and Commissioning Manual