7.2.11 LD0.DPHPTOC three-phase directional overcurrent fault
detection
Table 136: LD0.DPHPTOC three-phase directional overcurrent fault detection
Bit A
Reg A IEC 61850 name SA name Description Values
LD0.DPHPTOC1 SIM8F-1
524 384.12 .Str.general START General Start 1 = Start
525 384.13 .Str.phsA Phase A Start 1 = Start
526 384.14 .Str.phsB Phase B Start 1 = Start
527 384.15 .Str.phsC Phase C Start 1 = Start
528 385.00 .Op.general Operate General Operate 1 = Operate
529 385.01 .Op.phsA Phase A Operate 1 = Operate
530 385.02 .Op.phsB Phase B Operate 1 = Operate
531 385.03 .Op.phsC Phase C Operate 1 = Operate
538 385.10 .OpFwd.general Forward Operate 1 = Operate
539 385.11 .OpRev.general Reverse Operate 1 = Operate
LD0.DPHPTOC2 SIM8F-2
556 386.12 .Str.general START General Start 1 = Start
557 386.13 .Str.phsA Phase A Start 1 = Start
558 386.14 .Str.phsB Phase B Start 1 = Start
559 386.15 .Str.phsC Phase C Start 1 = Start
560 387.00 .Op.general Operate General Operate 1 = Operate
561 387.01 .Op.phsA Phase A Operate 1 = Operate
562 387.02 .Op.phsB Phase B Operate 1 = Operate
563 387.03 .Op.phsC Phase C Operate 1 = Operate
570 387.10 .OpFwd.general Forward Operate 1 = Operate
571 387.11 .OpRev.general Reverse Operate 1 = Operate
LD0.DPHPTOC3 SIM8F-3
652 800.12 .Str.general START General Start 1 = Start
653 800.13 .Str.phsA Phase A Start 1 = Start
654 800.14 .Str.phsB Phase B Start 1 = Start
655 800.15 .Str.phsC Phase C Start 1 = Start
656 801.00 .Op.general Operate General Operate 1 = Operate
657 801.01 .Op.phsA Phase A Operate 1 = Operate
658 801.02 .Op.phsB Phase B Operate 1 = Operate
659 801.03 .Op.phsC Phase C Operate 1 = Operate
666 801.10 .OpFwd.general Forward Operate 1 = Operate
667 801.11 .OpRev.general Reverse Operate 1 = Operate
LD0.DPHPTOC4 SIM8F-4
684 802.12 .Str.general START General Start 1 = Start
Table continues on next page
1MRS757488 H Section 7
Modbus TCP communication
RIO600 209
Installation and Commissioning Manual