7.2.26 LD0.DPHPTOC three-phase directional overcurrent fault
detection
Table 151: LD0.DPHPTOC three-phase directional overcurrent fault detection
Reg A
Type Scale IEC 61850 name SA name Description Values
LD0.DPHPTOC1 SIM8F-1 0 = unknown
1 = forward
2 = reverse
3 = both
408
u16 1 .Str.dirgeneral General Start
409 u16 1 .Str.dirphsA Phase A Start
410 u16 1 .Str.dirphsB Phase B Start
411 u16 1 .Str.dirphsC Phase C Start
LD0.DPHPTOC2 SIM8F-2
540 u16 1 .Str.dirgeneral General Start
541 u16 1 .Str.dirphsA Phase A Start
542 u16 1 .Str.dirphsB Phase B Start
543 u16 1 .Str.dirphsC Phase C Start
LD0.DPHPTOC3 SIM8F-3
872 u16 1 .Str.dirgeneral General Start
873 u16 1 .Str.dirphsA Phase A Start
874 u16 1 .Str.dirphsB Phase B Start
875 u16 1 .Str.dirphsC Phase C Start
LD0.DPHPTOC4 SIM8F-4
1004 u16 1 .Str.dirgeneral General Start
1005 u16 1 .Str.dirphsA Phase A Start
1006 u16 1 .Str.dirphsB Phase B Start
1007 u16 1 .Str.dirphsC Phase C Start
LD0.DPHPTOC5 SIM8F-5
1136 u16 1 .Str.dirgeneral General Start
1137 u16 1 .Str.dirphsA Phase A Start
1138 u16 1 .Str.dirphsB Phase B Start
1139 u16 1 .Str.dirphsC Phase C Start
Section 7 1MRS757488 H
Modbus TCP communication
220 RIO600
Installation and Commissioning Manual