7.2.31 LD0.PEMMXU power measurements
Table 156: LD0.PEMMXU power measurements
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.PEMMXU1 SIM8F-1
450 i32 1 .W.phsA.cVal.mag.f Phase A Active Power
451
452 i32 1 .W.phsB.cVal.mag.f Phase B Active Power
453
454 i32 1 .W.phsC.cVal.mag.f Phase C Active Power
455
456 i32 1 .TotW.mag.f Total Active Power
457
458 i32 1 .VAr.phsA.cVal.mag.f Phase A Reactive Power
459
460 i32 1 .VAr.phsB.cVal.mag.f Phase B Reactive Power
461
462 i32 1 .VAr.phsC.cVal.mag.f Phase C Reactive Power
463
464 i32 1 .TotVAr.mag.f Total Reactive Power
465
466 i32 1 .VA.phsA.cVal.mag.f Phase A Apparent Power
467
468 i32 1 .VA.phsB.cVal.mag.f Phase B Apparent Power
469
470 i32 1 .VA.phsC.cVal.mag.f Phase C Apparent Power
471
472 i32 1 .TotVA.mag.f Total Apparent Power
473
474 i32 100 .Hz.mag.f Frequency
475
476 i32 1000 .TotPF.mag.f Average Power Factor
477
LD0.PEMMXU2 SIM8F-2
582 i32 1 .W.phsA.cVal.mag.f Phase A Active Power
583
584 i32 1 .W.phsB.cVal.mag.f Phase B Active Power
585
586 i32 1 .W.phsC.cVal.mag.f Phase C Active Power
587
Table continues on next page
1MRS757488 H Section 7
Modbus TCP communication
RIO600 227
Installation and Commissioning Manual