Reg A Scale IEC 61850 name SA name Description Values
271 <reserved> <reserved> 0
LD0.AOMGGIO4
272 Value reported with a scale
factor of "1" when channel
configured as dimensionless
and with a scale factor of "100"
when channel configured as
mA
.AnOut1.mxVal.f
AOM 4-Channel 1 Output Value 0.0...20.0 [mA] /
-32768...+32768
1)
273 .AnOut2.mxVal.f AOM 4-Channel 2 Output Value 0.0...20.0 [mA] /
-32768...+32767
1)
274 .AnOut3.mxVal.f AOM 4-Channel 3 Output Value 0.0...20.0 [mA] /
-32768...+32768
1)
275 .AnOut4.mxVal.f AOM 4-Channel 4 Output Value 0.0...20.0 [mA] /
-32768...+32768
1)
276 <reserved> <reserved> 0
277 <reserved> <reserved> 0
278 <reserved> <reserved> 0
279 <reserved> <reserved> 0
280 <reserved> <reserved> 0
281 <reserved> <reserved> 0
282 <reserved> <reserved> 0
283 <reserved> <reserved> 0
284 <reserved> <reserved> 0
285 <reserved> <reserved> 0
286 <reserved> <reserved> 0
287 <reserved> <reserved> 0
1) As per user configuration
7.2.10 LD0.PHPTOC phase overcurrent fault detection
Table 135: LD0.PHPTOC phase overcurrent fault detection
Bit A
Reg A IEC 61850 name SA name Description Values
LD0.PHPTOC1 SIM8F-1/SIM4F-1
516 384.04 .Str.general START General Start 1 = Start
517 384.05 .Str.phsA Phase A Start 1 = Start
518 384.06 .Str.phsB Phase B Start 1 = Start
519 384.07 .Str.phsC Phase C Start 1 = Start
520 384.08 .Op.general Operate General Operate 1 = Operate
521 384.09 .Op.phsA Phase A Operate 1 = Operate
522 384.10 .Op.phsB Phase B Operate 1 = Operate
523 384.11 .Op.phsC Phase C Operate 1 = Operate
LD0.PHPTOC2 SIM8F-2/SIM4F-2
548 386.04 .Str.general START General Start 1 = Start
549 386.05 .Str.phsA Phase A Start 1 = Start
Table continues on next page
1MRS757488 H Section 7
Modbus TCP communication
RIO600 207
Installation and Commissioning Manual