EasyManua.ls Logo

ABB Remote I/O RIO600 - LD0.VMMXU Voltage Measurements

ABB Remote I/O RIO600
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reg A Type Scale IEC 61850 name SA name Description Values
1015
1016 i32 1 .A.phsB.cVal.ang.f Phase B Current Angle
1017
1018 i32 10 .A.phsC.cVal.mag.f Phase C Current Magnitude
1019
1020 i32 1 .A.phsC.cVal.ang.f Phase C Current Angle
1021
LD0.CMMXU5 SIM8F-5/SIM4F-5
1142 i32 10 .A.phsA.cVal.mag.f Phase A Current Magnitude
1143
1144 i32 1 .A.phsA.cVal.ang.f Phase A Current Angle
1145
1146 i32 10 .A.phsB.cVal.mag.f Phase B Current Magnitude
1147
1148 i32 1 .A.phsB.cVal.ang.f Phase B Current Angle
1149
1150 i32 10 .A.phsC.cVal.mag.f Phase C Current Magnitude
1151
1152 i32 1 .A.phsC.cVal.ang.f Phase C Current Angle
1153
7.2.30 LD0.VMMXU voltage measurements
Table 155: LD0.VMMXU voltage measurements
Reg A
Type Scale IEC 61850 name SA name Description Values
LD0.VMMXU1 SIM8F-1
426 i32 1 .PPV.phsAB.cVal.mag.f V
ab
Magnitude
427
428 i32 1 .PPV.phsAB.cVal.ang.f V
ab
Angle
429
430 i32 1 .PPV.phsBC.cVal.mag.f V
bc
Magnitude
431
432 i32 1 .PPV.phsBC.cVal.ang.f V
bc
Angle
433
434 i32 1 .PPV.phsCA.cVal.mag.f V
ca
Magnitude
435
436 i32 1 .PPV.phsCA.cVal.ang.f V
ca
Angle
437
Table continues on next page
1MRS757488 H Section 7
Modbus TCP communication
RIO600 223
Installation and Commissioning Manual

Table of Contents

Related product manuals