LECM with copper interface LECM with fiber interface
Description Modules Channels Modules Channels
Analog output modules 2 8 1 4
SIM8F/SIM4F modules 5 - 4 -
Smart control module (SCM8H/
SCM8L)
3 24 2 16
Table 3: Maximum number of modules and channels available when two power supply
modules are connected
LECM with copper interface LECM with fiber interface
Description Modules Channels Modules Channels
Digital input modules (DIM8H/
DIM8L)
5 40 5 40
Digital output modules 10 40 9 36
RTD4 modules 10 40 9 36
Analog output modules 4 16 3 12
SIM8F/SIM4F modules 5 - 5 -
Smart control module (SCM8H/
SCM8L)
5 40 5 40
A combination of all the modules can be used in a single RIO600 stack. The number
of modules supported by a number of power supply modules is automatically checked
by PCM600. If the selected combination of modules exceeds the number of supported
modules related to power consumption, the configuration tool gives an indication and
does not configure the stack.
3.3 Web HMI
The WHMI allows accessing the present status information of RIO600 via a Web
browser. The supported Web browser version is Internet Explorer 9.0 or later and the
preferred version is Internet Explorer 10.
1MRS757488 H Section 3
RIO600 overview
RIO600 19
Installation and Commissioning Manual