Signals
Table 81: PHSVPR Output signals
Name
Type Description
PHSVPR_ULive Boolean Indicating voltage presence
PHSVPR_UDead Boolean Indicating voltage absence
Settings
Table 82: PHSVPR Settings
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
Alive Phase
Supervision
1 out of 3
2 out of 3
3 out of 3
-
- 1 out of 3 Number of phases
required for voltage
presence detection
Dead Phase
Supervision
1 out of 3
2 out of 3
3 out of 3
-
- 3 out of 3 Number of phases
required for voltage
absence detection
Voltage Live Value
300…25000 V 1 6000 Limit for phase to
neutral voltage
presence detection
Voltage Dead Value
300…25000 V 1 300 Limit for phase to
neutral voltage
absence detection
Table 83: PHSVPR Technical data
Characteristic
Value
Operation accuracy At frequency f = f
n
±5% in the range of 480 V...9.6 kV
±0.5% in the range of 9.6...28.8 kV
6.1.6.7 Negative-sequence overcurrent indication NSPTOC
Identification
Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative-sequence overcurrent
protection
NSPTOC I2> 46
Functionality
The negative-sequence overcurrent protection function NSPTOC is used to increase
sensitivity to detect single-phase and phase-to-phase faults or unbalanced loads due
to, for example, broken conductors or unsymmetrical feeder voltages.
1MRS757488 H Section 6
Commissioning
RIO600 137
Installation and Commissioning Manual