7.2.27 LD0.EFPTOC non-directional earth-fault detection
Table 152: LD0.EFPTOC non-directional earth-fault detection
Reg A
Type Scale IEC 61850 name SA name Description Values
412 u16 LD0.EFPTOC1 SIM8F-1/SIM4F-1 0 = unknown
1 = forward
2 = reverse
3 = both
1 .Str.dirgeneral General Start
544 u16 LD0.EFPTOC2 SIM8F-2/SIM4F-2
1 .Str.dirgeneral General Start
876 u16 LD0.EFPTOC3 SIM8F-3/SIM4F-3
1 .Str.dirgeneral General Start
1008 u16 LD0.EFPTOC4 SIM8F-4/SIM4F-4
1 .Str.dirgeneral General Start
1140 u16 LD0.EFPTOC5 SIM8F-5/SIM4F-5
1 .Str.dirgeneral General Start
7.2.28 LD0.DEFPTOC directional earth-fault detection
Table 153: LD0.DEFPTOC directional earth-fault detection
Reg A
Type Scale IEC 61850 name SA name Description Values
LD0.DEFPTOC1 SIM8F-1 0 = unknown
1 = forward
2 = reverse
3 = both
413
u16 1 .Str.dirgeneral General Start
LD0.DEFPTOC2 SIM8F-2
545 u16 1 .Str.dirgeneral General Start
LD0.DEFPTOC3 SIM8F-3
877 u16 1 .Str.dirgeneral General Start
LD0.DEFPTOC4 SIM8F-4
1009 u16 1 .Str.dirgeneral General Start
LD0.DEFPTOC5 SIM8F-5
1141 u16 1 .Str.dirgeneral General Start
7.2.29 LD0.CMMXU phase current measurements
Table 154: LD0.CMMXU phase current measurements
Reg A
Type Scale IEC 61850 name SA name Description Values
LDO.CMMXU1 SIM8F-1/SIM4F-1
414 i32 10 .A.phsA.cVal.mag.f Phase A Current Magnitude
415
416 i32 1 .A.phsA.cVal.ang.f Phase A Current Angle
417
418 i32 10 .A.phsB.cVal.mag.f Phase B Current Magnitude
Table continues on next page
1MRS757488 H Section 7
Modbus TCP communication
RIO600 221
Installation and Commissioning Manual