Table 21: Operating parameter settings for DIM8H and DIM8L
Parameter name Range Unit Default value Description
Debounce Time 5...4095 ms 10 This parameter is the debounce time for the DIM8
module in ms.
Oscillation Upper Limit 2...63 Counts 63 This parameter is the oscillation suppression
upper limit.
The parameter value acts as the count for upper
limit.
Oscillation Suppression
Hysteresis
1...62 Counts 62 This parameter is the oscillation suppression
Hysteresis.
The parameter value acts as the count for
Hysteresis.
Oscillation Time
0...4095 ms 4095 This parameter is the oscillation suppression time
limit. The parameter value acts as the time
window for the oscillation detection in ms.
0 means that no oscillation suppression is active.
Description
Digital Input 1...8 User defined channel name not exceeding 30
characters
Channel 1 Inversion Non-Inverted/Inverted Non Inverted channel 1 input type: non-inverted/inverted
Channel 2 Inversion Non-Inverted/Inverted Non Inverted channel 2 input type: non-inverted/inverted
Channel 3 Inversion Non-Inverted/Inverted Non Inverted channel 3 input type: non-inverted/inverted
Channel 4 Inversion Non-Inverted/Inverted Non Inverted channel 4 input type: non-inverted/inverted
Channel 5 Inversion Non-Inverted/Inverted Non Inverted channel 5 input type: non-inverted/inverted
Channel 6 Inversion Non-Inverted/Inverted Non Inverted channel 6 input type: non-inverted/inverted
Channel 7 Inversion Non-Inverted/Inverted Non Inverted channel 7 input type: non-inverted/inverted
Channel 8 Inversion Non-Inverted/Inverted Non Inverted channel 8 input type: non-inverted/inverted
Input Channel 1 Enabled/
Disabled
Enabled/Disabled Enabled channel 1: enabled/disabled
Input Channel 2 Enabled/
Disabled
Enabled/Disabled Enabled channel 2 : enabled/disabled
Input Channel 3 Enabled/
Disabled
Enabled/Disabled Enabled channel 3: enabled/disabled
Input Channel 4 Enabled/
Disabled
Enabled/Disabled Enabled channel 4: enabled/disabled
Input Channel 5 Enabled/
Disabled
Enabled/Disabled Enabled channel 5: enabled/disabled
Input Channel 6 Enabled/
Disabled
Enabled/Disabled Enabled channel 6: enabled/disabled
Input Channel 7 Enabled/
Disabled
Enabled/Disabled Enabled channel 7: enabled/disabled
Input Channel 8 Enabled/
Disabled
Enabled/Disabled Enabled channel 8: enabled/disabled
6.1.2.1 Binary input debounce time (filter time)
The filter time eliminates debounces and short disturbances on a binary input. The
filter time is set for each binary input.