Description PSMH PSML
Maximum interruption time in
the auxiliary DC without
resetting the RIO600 modules
100 ms at U
aux
nominal 50 ms at U
aux
nominal
Ripple in the DC auxiliary
voltage
Max. 15% of the DC value (at frequency of 100 Hz)
Reversal of DC power supply
polarity
1 minute for each polarity
Burden of auxiliary voltage
supply
Quiescent (Pq) condition
(none of the 20 I/O
channels are activated)
<4.0 W nominal
Operating condition (20
binary output channels in
DOM4 modules are
activated)
<12.0 W (maximum)
Module configuration Condition Max. consumption for PSMH
and PSML
PSM + LECM + DIM8H All DIs activated 2 W
PSM + LECM + DIM8L
PSM + LECM + DOM4 All DOs activated 4 W
PSM + LECM + DOM4 (5) All DOs activated 12 W
PSM (2) + LECM + DIM8H (5) All DIs activated 11 W
PSM (2) + LECM + DIM8L (5)
PSM (2) + LECM + DOM4 (10) All DOs activated 22 W
Table 191: Binary inputs
Description
DIM8H DIM8L
Rated voltage 110…250 V DC 24, 30, 48, 60 V DC
Operating voltage range ±20% of rated voltage ±20% of rated voltage
Current drain 3…3.7 mA 2 mA
Power consumption/input
channel 330…925 mW 30…130 mW
Threshold voltage 78 V DC 13 V DC
Reaction time 5 ms...4.0 s filtering time 5 ms...4.0 s filtering time
Table 192: Signal outputs (digital output module DOM4)
Description
Value
Operating time <5 ms
Nominal coil power <500 mW
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Table continues on next page
Section 10 1MRS757488 H
Technical data
286 RIO600
Installation and Commissioning Manual