Description Value
Make and carry for 3.0 s 10 A
Make and carry for 0.5 s 15 A
Breaking capacity when the control circuit time
constant L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Table 193: mA/RTD input (RTD4 module)
Description Value
RTD inputs Supported RTD
sensors
100 Ω platinum TCR 0.00385 (DIN
43760)
250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN
43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
Maximum lead
resistance (three-wire
measurement)
100 Ω platinum
200 Ω per lead
250 Ω platinum 200 Ω per lead
100 Ω nickel 200 Ω per lead
120 Ω nickel 200 Ω per lead
250 Ω nickel 200 Ω per lead
Isolation 4 kV Inputs to all other
channel outputs and
protective earth
RTD/resistance
sensing maximum
0.275 mA rms current
Operation accuracy ±1°C
Response time < Filter time + 350 ms
mA inputs Supported current
range
0…20 mA
Current input
impedance
44 Ω ± 0.1%
Operation accuracy ±0.5% or ±0.1 mA
Isolation 4 kV Inputs to all outputs and
protective earth
Table 194: Analog output module (AOM4)
Description
Value
mA output Supported current
range
0.0…20.0 mA
Operation accuracy ±0.1% or ±0.2 mA
Isolation 4 kV between each output and protective earth
1MRS757488 H Section 10
Technical data
RIO600 287
Installation and Commissioning Manual