Table 90: SEQSPV Output signals
Name Type Description
FUSEF_U BOOLEAN General start of function
Settings
Table 91: SEQSPVC Settings
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
Neg Seq Current
Lev
4…1000 A 1 12 Operate level of neg
seq undercurrent
element
Neg Seq Voltage
Lev
300…10000 V 5 1500 Operate level of neg
seq overvoltage
element
Current Change
Rate
4…1000 A 1 60 Operate level of
change in phase
current
Voltage Change
Rate
300…10000 V 5 6000 Operate level of
change in phase
voltage
Change Rate
Enable
FALSE
TRUE
- - FALSE Enabling operation
of change based
function
Min Op Voltage
Delta
300…10000 V 5 7500 Minimum operate
level of phase
voltage for delta
calculation
Min Op Current
Delta
4…1000 A 1 40 Minimum operate
level of phase
current for delta
calculation
Seal in Voltage
300…10000 V 5 7500 Operate level of
seal-in phase
voltage
Enable Seal In
FALSE
TRUE
- - FALSE Enabling seal in
functionality
Current Dead Lin Val 4…1000 A 1 20 Operate level for
open phase current
detection
Table 92: SEQSPVC Technical data
Characteristic
Value
Operate time accuracy Depending on the nominal frequency of the
current measured: f
n
NPS function:
<36 ms for U
Fault
= 1.1 × set value
<22 ms for U
Fault
= 5 × set value
Delta function:
<34 ms for ΔU = 1.1 × set value
<28 ms for ΔU = 5 × set value
1MRS757488 H Section 6
Commissioning
RIO600 143
Installation and Commissioning Manual