Table 104: Operation parameters for three-position earthing switch, two-position earthing switch, two-position disconnector switch or
circuit breaker control application
Parameter name Range Unit Default value Description
Motor Parameters
Motor start time out 0...32000 ms 0 Maximum time from
Starting motor to
definitely leave defined
Start position
Motor braking
Not used/used Not used Motor braking
Motor U
nominal
24…250 VDC 110 Motor nominal voltage
Motor(s) duty cycle 1…100 % 100 Duty cycle to run motor(s)
Earthing switch
parameters
Earthing switch close
time-out
0…32000 ms 25000 Maximum time from
Earthing switch opened
to Earthing switch closed
Earthing switch open
time-out
0…32000 ms 25000 Max time from Earthing
switch closed to Earthing
switch opened
Disconnector parameters
Disconnector close time-
out
0…32000 ms 25000 Maximal time from
Disconnector opened to
Disconnector closed
Disconnector open time-
out
0…32000 ms 25000 Maximal time from
Disconnector closed to
Disconnector opened
CB parameters
Trip coil pulse time 1...500 ms 100 Pulse time for trip coil
Pulse ends if start
position leaved or end
position reached
Closing coil pulse time
1...500 ms 100 Pulse time for closing coil
Pulse ends if start
position leaved or end
position reached
Input channels
Debounce Time (Filter
time)
5...4095 ms 10 This parameter is the
debounce time for the
input signal in ms.
Oscillation Upper Limit
2...63 Counts 63 This parameter is the
oscillation suppression
upper limit.
The parameter value acts
as the count for upper
limit.
Oscillation Suppression
Hysteresis
1...62 Counts 62 This parameter is the
oscillation suppression
hysteresis.
The parameter value acts
as the count for
hysteresis.
Table continues on next page
Section 6 1MRS757488 H
Commissioning
160 RIO600
Installation and Commissioning Manual