Bit A Reg A IEC 61850 name SA name Description Values
1760 1522 .Ind1.stVal Digital Input Channel 1 0/1 = Off/On
1761 1522.01 .Ind2.stVal Digital Input Channel 2 0/1 = Off/On
1762 1522.02 .Ind3.stVal Digital Input Channel 3 0/1 = Off/On
1763 1522.03 .Ind4.stVal Digital Input Channel 4 0/1 = Off/On
1764 1522.04 RELEASE_ES Release Earth Switch
Information
0/1 = Off/On
1765 1522.05 RELEASE_DS Release Disconnector
Information
0/1 = Off/On
1766 1522.06 REED_ES REED Earth Switch
Information
0/1 = Off/On
1767 1522.07 RELEASE_CB Release Circuit Breaker
Information
0/1 = Off/On
1768 1522.08 .Ind10.stVal Error Code: No Fault 0/1 = Off/On
1769 1522.09 .Ind11.stVal Error Code: Device Error 0/1 = Off/On
1770 1522.1 .Ind12.stVal Error code: Release 0/1 = Off/On
1771 1522.11 .Ind13.stVal Error Code: No Act 0/1 = Off/On
1772 1522.12 .Ind14.stVal Error Code: Interlocking Error 0/1 = Off/On
1773 1522.13 .Ind15.stVal Error Code: REED/ Release
Error
0/1 = Off/On
1774 1522.14 .Ind16.stVal Error Code: Position Error 0/1 = Off/On
1775 1522.15 .Ind17.stVal Error Code: Time-out Error 0/1 = Off/On
1776 1523 .CircAlm.stVal Trip Circuit Supervision Alarm
Status
0/1 = Off/On
1777 1523.01 .CircAlm.stVal Trip Circuit Supervision Alarm
Status
0/1 = Off/On
1)
1. LD0.SCMLGGIO5/
LD0.SCMHGGIO5
2. LD0.SCMLPGGIO5/
LD0.SCMHPGGIO5
3. LD0.SCMLDGGIO5/
LD0.SCMHDGGIO5
4. LD0.SCMLEGGIO5/
LD0.SCMHEGGIO5
5. LD0.SCMLCGGIO5/
LD0.SCMHCGGIO5
6. LD0.TCSLSCBR5/
LD0.TCSHSCBR5
SCM-5
1792 1524 .Ind1.stVal Digital Input Channel 1 0/1 = Off/On
1793 1524.01 .Ind2.stVal Digital Input Channel 2 0/1 = Off/On
1794 1524.02 .Ind3.stVal Digital Input Channel 3 0/1 = Off/On
1795 1524.03 .Ind4.stVal Digital Input Channel 4 0/1 = Off/On
1796 1524.04 RELEASE_ES Release Earth Switch
Information
0/1 = Off/On
1797 1524.05 RELEASE_DS Release Disconnector
Information
0/1 = Off/On
1798 1524.06 REED_ES REED Earth Switch
Information
0/1 = Off/On
Table continues on next page