Bit A Reg A IEC 61850 name SA name Description Values
2510 1568.14 <reserved> <reserved>
2511 1568.15 OPEN_CB Circuit Breaker Open
Command
0/1 = Off/On
2512 1569.00 CLOSE_CB Circuit breaker Close
Command
0/1 = Off/On
2513 1569.01 <reserved> <reserved>
1)
1. LD0.SCMLGGIO2/
LD0.SCMHGGIO2
2. LD0.SCMLPGGIO2/
LD0.SCMHPGGIO2
3. LD0.SCMLDGGIO2/
LD0.SCMHDGGIO2
4. LD0.SCMLEGGIO2/
LD0.SCMHEGGIO2
5. LD0.SCMLCGGIO2/
LD0.SCMHCGGIO2
SCM-2
2528 1570.00 .SPCSO1.stVal Digital Output Channel 1 0/1 = Off/On
2529 1570.01 .SPCSO2.stVal Digital Output Channel 2 0/1 = Off/On
2530 1570.02 .SPCSO3.stVal Digital Output Channel 3 0/1 = Off/On
2531 1570.03 .SPCSO4.stVal Digital Output Channel 4 0/1 = Off/On
2532 1570.04 <reserved> <reserved>
2533 1570.05 <reserved> <reserved>
2534 1570.06 <reserved> <reserved>
2535 1570.07 <reserved> <reserved>
2536 1570.08 CLOSE_ES Earth Switch Close Command 0/1 = Off/On
2537 1570.09 OPEN_ES Earth Switch Open Command 0/1 = Off/On
2538 1570.10 CLOSE_DS Disconnector Close Command 0/1 = Off/On
2539 1570.11 OPEN_DS Disconnector Open Command 0/1 = Off/On
2540 1570.12 <reserved> <reserved>
2541 1570.13 <reserved> <reserved>
2542 1570.14 <reserved> <reserved>
2543 1570.15 OPEN_CB Circuit Breaker Open
Command
0/1 = Off/On
2544 1571.00 CLOSE_CB Circuit breaker Close
Command
0/1 = Off/On
2545 1571.01 <reserved> Digital Output Channel 1
1)
1. LD0.SCMLGGIO3/
LD0.SCMHGGIO3
2. LD0.SCMLPGGIO3/
LD0.SCMHPGGIO3
3. LD0.SCMLDGGIO3/
LD0.SCMHDGGIO3
4. LD0.SCMLEGGIO3/
LD0.SCMHEGGIO3
5. LD0.SCMLCGGIO3/
LD0.SCMHCGGIO3
SCM-3
2560 1572.00 .SPCSO1.stVal Digital Output Channel 1 0/1 = Off/On
Table continues on next page
Section 7 1MRS757488 H
Modbus TCP communication
252 RIO600
Installation and Commissioning Manual