EasyManua.ls Logo

ABB Remote I/O RIO600 - Table 199: Communication interface (communication module LECM)

ABB Remote I/O RIO600
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 199: Communication interface (communication module LECM)
Connector Cable Data transfer Maximum
distance
Wave length Permitted
path
attenuation
1)
RJ-45 Shielded twisted pair
cable, at minimum CAT5e
10/100
Mbits/s
30 m - -
LC Multimode 62.5/125 μm or
50/125 μm glass-fiber core
100 Mbits/s 2 km 1310 nm <8 dB
1) Maximum allowed attenuation caused by connectors and cable together
Table 200: Degree of protection by enclosure
Description Value
Degree of protection
IP20
1)
1) If a higher IP class is required, the cabinet where the device is installed should provide proper
protection.
Table 201: Environmental conditions
Description Value
Operating temperature range -25...+70°C
Relative humidity <93%
Atmospheric pressure 86...106 kPa
Altitude up to 2000 m
Transport and storage temperature range -40...+85°C