Loading...
SCM8H / SCM8L
DI 1
DI 2
DI 3
DI 4
X1
0V-
DI1
DI2
DI3
DI4
0V-
1
2
3
4
5
6
X2
-
HS1
HS2
HS3
HS4
+
1
2
3
4
5
6
L-
L+
M
Disconnector CLOS
E
Disconnector OPEN
COM for DI3 and DI4
HS1
HS2
HS3
HS4
GUID-B93E3F33-5A6E-42D1-9240-B9E860B0E4F0 V2 EN
Figure 29: Connection diagram for two-position disconnector switch application
(rod type with DC motor)
Table 17: SCM connection for two-position disconnector switch application
X1
Connector
inputs
Description X2 Connector
outputs
Description
OV- 1 Common
return for DI1
and DI2
-
1 AUX. DC
voltage L-
DI1 2 Digital input 1 HS1 2 DC motor
connection
DI2 3 Digital input 2 HS2 3 DC motor
connection
DI3 4 Disconnector
switch CLOSE
position signal
HS3
4 DC motor
connection
DI4 5 Disconnector
switch OPEN
position signal
HS4
5 DC motor
connection
OV- 6 Common
return for DI3
and DI4
+
6 AUX. DC
voltage L+
1MRS757488 H Section 5
Installing
RIO600 51
Installation and Commissioning Manual

Table of Contents

Related product manuals