Table 49: EMMTR Output signals
Name Type Description
DmdWh REAL Accumulated forward active
energy value in kWh
SupWh REAL Accumulated reverse active
energy value in kWh
DmdVArh REAL Accumulated forward reactive
energy value in kVArh
SupVArh REAL Accumulated reverse reactive
energy value in kVArh
Table 50: EMMTR Technical data
Characteristic Value
Operation accuracy At frequency f = fn
All three voltages are in the range of 9.6...14.4 kV
or 19.2...28.8 kV.
All three currents are in the range of 80...630 A.
Active power and energy are in the range |PF| >
0.71.
Reactive power and energy are in the range |PF| <
0.71.
±3.0% for energy
Suppression of harmonics RMS: No suppression
Current, voltage and power average and peak measurement CMSTA,
VMSTA, PEMSTA
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current, voltage and power average and
peak measurement
CMSTA,
VMSTA,
PEMSTA
-
-
Section 6 1MRS757488 H
Commissioning
82 RIO600
Installation and Commissioning Manual