The OP GENERAL output is available at LED 5 of the SIM8F module.
The phase segregated as well as general start and operate outputs STR GENERAL,
STR PHSA, STR PHSB, STR PHSC, OP GENERAL, OP PHSA, OP PHSB and OP
PHSC are available over communication.
Signals
Table 60: PHPTOC Output signals
Name Type Description
Op general Boolean General operate signal
Op phsA Boolean Operate signal for phase A
Op phsB Boolean Operate signal for phase B
Op phsC Boolean Operate signal for phase C
Str general Boolean General start signal
Str phsA Boolean Start signal for phase A
Str phsB Boolean Start signal for phase B
Str phsC Boolean Start signal for phase C
Settings
Table 61: PHPTOC Settings
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
No. of Start Phases 1 out of 3
2 out of 3
3 out of 3
-
- 1 out of 3 Number of phases
required for operate
activation
Start Value
50…2000 A 10 480 Start value for
overcurrent fault
detection
Operate Delay Time
40…60000 ms 10 40 Operate delay time
Absolute Hysteresis 0.0…100.0 A 0.1 3.0 Absolute hysteresis
for current
Table 62: PHPTOC Technical data
Charateristic
Value
Operation accuracy Depending on the frequency of the current
measured: f = f
n
±1.5% of the set value
Operate time accuracy (DMT)
±1.0% of the set value or ±20 ms
1MRS757488 H Section 6
Commissioning
RIO600 91
Installation and Commissioning Manual