EasyManuals Logo

ABB RET670 Applications Manual

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #152 background imageLoading...
Page #152 background image
It is strongly recommended to use the highest tap of the CT whenever
high impedance protection is used. This helps in utilizing maximum CT
capability, minimize the current, thereby reducing the stability voltage
limit. Another factor is that during internal faults, the voltage developed
across the selected tap is limited by the non-linear resistor but in the
unused taps, owing to auto-transformer action, voltages may be much
higher than design limits might be induced.
Setting example
Basic data:
Current transformer ratio: 2000/5A
CT Class: C800 (At max tap of 2000/5A)
Secondary resistance: 0.5 Ohm (2000/5A tap)
Cable loop resistance:
2
<200 ft AWG10 (one way between the junction point and the
farthest CT) to be limited to approx. 0.2 Ohms at 75deg C gives
loop resistance 2 · 0.2 = 0.4 Ohms.
Max fault current: Equal to switchgear rated fault current 40 kA
Calculation:
( )
40000
0.5 0.4 90
400
VR V> × + =
EQUATION1751-ANSI V1 EN (Equation 36)
Select a setting of
TripPickup
=100 V.
The current transformer saturation voltage must be at least, twice the set operating voltage
TripPickup
.
(0.5 8) 100 *0.7 595VkneeANSI V> + × =
EQUATION1752-ANSI V1 EN (Equation 37)
that is, bigger than 2 ·
TripPickup
Check from the table of selected resistances the required series stabilizing resistor
value to use. As this application requires to be so sensitive select R Series= 500 ohm,
which gives an IED operating current of 200 mA.
Calculate the primary sensitivity at operating voltage, ignoring the current drawn by
the non-linear resistor.
Section 3 1MRK504116-UUS C
IED application
146
Application manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals