3.6.11.2 Setting guidelines
Setting guidelines are prepared in the form of a setting example for the protected power
line as part of a two-machine system presented in figure 160.
99001019_ansi.vsd
~~
E
A
d
A
= const
d
B
= f(t)
E
B
A B
Z
SA
Z
SB
Z
L
R
ANSI99001019 V1 EN
Figure 160: Protected power line as part of a two-machine system
Reduce the power system with protected power line into equivalent two-machine
system with positive sequence source impedances Z
SA
behind the IED and Z
SB
behind
the remote end bus B. Observe a fact that these impedances can not be directly
calculated from the maximum three-phase short circuit currents for faults on the
corresponding busbar. It is necessary to consider separate contributions of different
connected circuits.
The required data is as follows:
EQUATION1728 V1 EN
Rated system voltage
EQUATION1729 V1 EN
Minimum expected system voltage under critical system
conditions
EQUATION1730 V1 EN
Rated system frequency
EQUATION1731 V1 EN
Rated primary voltage of voltage protection transformers used
EQUATION1732 V1 EN
Rated secondary voltage of voltage instrument transformers used
Table continues on next page