4.2.6.2 Setting guidelines
Redundant communication (DUODRV) is configured in the local HMI under Main
menu/Settings/General settings/Communication/Ethernet configuration/Rear
OEM - Redundant PRP
The settings can then be viewed, but not set, in the Parameter Setting tool in PCM600
under Main menu/IED Configuration/Communication/Ethernet configuration/
DUODRV:
Operation: The redundant communication will be activated when this parameter is set
to On.After confirmation the IED will restart and the setting alternatives Rear OEM -
Port AB and CD will not be further displayed in the local HMI. The ETHLANAB and
ETHLANCD in the Parameter Setting Tool are irrelevant when the redundant
communication is activated, only DUODRV IPAdress and IPMask are valid.
1MRK504116-UUS C Section 4
Station communication
815
Application manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals