The value of k=0.92 is recommended in generator applications as the trip delay is
normally quite long.
The calibration factors for current and voltage measurement errors are set % of rated
current/voltage:
IMagComp5, IMagComp30, IMagComp100
VMagComp5, VMagComp30, VMagComp100
IMagComp5, IMagComp30, IMagComp100
The angle compensation is given as difference between current and voltage angle errors.
The values are given for operating points 5, 30 and 100% of rated current/voltage. The
values should be available from instrument transformer test protocols.
3.7.10.3 Setting parameters
Table 110: GUPPDUP (37) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disable / Enable
OpMode1 Disabled
UnderPower
- - UnderPower Operation mode 1
Power1 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 1 in % of Sbase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 1
TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1
DropDelay1 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 1
OpMode2 Disabled
UnderPower
- - UnderPower Operation mode 2
Power2 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 2 in % of Sbase
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 2
TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2
DropDelay2 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 2
Table 111: GUPPDUP (37) Group settings (advanced)
Name
Values (Range) Unit Step Default Description
TD 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 1 in % Sbase
Hysteresis2 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 2 in % Sbase
Table continues on next page
1MRK504116-UUS C Section 3
IED application
483
Application manual