3.12.8.2 Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GGIO) function are
set via the local HMI or PCM600.
Operation: turning the function operation Enabled/Disabled.
There are two settings for every command output (totally 8):
Latchedx: decides if the command signal for output x is Latched (steady) or Pulsed.
tPulsex: if Latchedx is set to Pulsed, then tPulsex will set the length of the pulse (in
seconds).
3.12.8.3 Setting parameters
Table 175: SPC8GGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
Latched1 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 1
tPulse1 0.01 - 6000.00 s 0.01 0.10 Output1 Pulse Time
Latched2 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 2
tPulse2 0.01 - 6000.00 s 0.01 0.10 Output2 Pulse Time
Latched3 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 3
tPulse3 0.01 - 6000.00 s 0.01 0.10 Output3 Pulse Time
Latched4 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 4
tPulse4 0.01 - 6000.00 s 0.01 0.10 Output4 Pulse Time
Latched5 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 5
tPulse5 0.01 - 6000.00 s 0.01 0.10 Output5 Pulse Time
Latched6 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 6
tPulse6 0.01 - 6000.00 s 0.01 0.10 Output6 Pulse Time
Latched7 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 7
tPulse7 0.01 - 6000.00 s 0.01 0.10 Output7 Pulse Time
Latched8 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 8
tPulse8 0.01 - 6000.00 s 0.01 0.10 Output8 pulse time
Section 3 1MRK504116-UUS C
IED application
710
Application manual