3.4.10.1 Application
The Signal matrix for binary outputs function SMBO is used within the Application
Configuration tool in direct relation with the Signal Matrix tool. SMBO represents the
way binary outputs are sent from one IED configuration.
It is important that SMBO inputs are connected when SMBOs are
connected to physical outputs through the Signal Matrix Tool. If
SMBOs are connected (in SMT) but their inputs not, all the
physical outputs will be set by default. This might cause
malfunction of primary equipment and/or injury to personnel.
3.4.10.2 Setting guidelines
There are no setting parameters for the Signal matrix for binary outputs SMBO
available to the user in Parameter Setting tool. However, the user must give a name to
SMBO instance and SMBO outputs, directly in the Application Configuration tool.
These names will define SMBO function in the Signal Matrix tool.
3.4.10.3 Setting parameters
The function does not have any parameters available in local HMI or PCM600.
3.4.11 Signal matrix for mA inputs SMMI
3.4.11.1 Application
The Signal matrix for mA inputs function SMMI is used within the Application
Configuration tool in direct relation with the Signal Matrix tool. SMMI represents the
way milliamp (mA) inputs are brought in for one IED configuration.
3.4.11.2 Setting guidelines
There are no setting parameters for the Signal matrix for mA inputs SMMI available to
the user in the Parameter Setting tool. However, the user must give a name to SMMI
instance and SMMI inputs, directly in the Application Configuration tool.
3.4.11.3 Setting parameters
The function does not have any parameters available in the local HMI or PCM600.