ABB RET670 - Horizontal Communication Via GOOSE for Interlocking GOOSEINTLKRCV

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
connection between the two lines of the diameter in the breaker-and-a-half switchyard
layout.
For a breaker-and-a-half arrangement, the modules BH_LINE_A, BH_CONN and
BH_LINE_B must be used.
Configuration setting
For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
989_OP = 1
989_CL = 0
989G_OP = 1
989G_CL = 0
If, in this case, line voltage supervision is added, then rather than setting 989 to open
state, specify the state of the voltage supervision:
989_OP = VOLT_OFF
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
VOLT_OFF = 1
VOLT_ON = 0
3.12.3.10 Horizontal communication via GOOSE for interlocking GOOSEINTLKRCV
Table 157: GOOSEINTLKRCV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
3.12.4 Voltage control
1MRK504116-UUS C Section 3
IED application
651
Application manual