Name Values (Range) Unit Step Default Description
Scale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output to unit
per counted value
Quantity Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
- - Count Measured quantity for SCAL_VAL output
tReporting 0 - 3600 s 1 60 Cycle time for reporting of counter value
3.16.2 Function for energy calculation and demand handling
ETPMMTR
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Energy calculation and demand
handling
ETPMMTR -
3.16.2.1 Application
Energy calculation and demand handling function ETPMMTR is intended for statistics
of the forward and reverse active and reactive energy. It has a high accuracy basically
given by the measurements function (CVMMXN). This function has a site calibration
possibility to further increase the total accuracy.
The function is connected to the instantaneous outputs of (CVMMXN) as shown in
figure 311.
P
Q
STACC
RSTACC
RSTDMD
TRUE
FALSE
FALSE
CVMMXN
IEC09000106.vsd
ETPMMTR
P_INST
Q_INST
IEC09000106 V1 EN
Figure 311: Connection of energy calculation and demand handling function
ETPMMTR to the measurements function (CVMMXN)
The energy values can be read through communication in MWh and MVarh in
monitoring tool of PCM600 and/or alternatively the values can be presented on the
local HMI. The local HMI graphical display is configured with PCM600 Graphical
Section 3 1MRK504116-UUS C
IED application
804
Application manual