Control Protection Control ProtectionControl and protection
GOOSE
en05000734.vsd
Station HSI
MicroSCADA
Gateway
IED
A
IED
A
IED
A
IED
A
IED
A
IEC05000734 V1 EN
Figure 313: Example of a broadcasted GOOSE message
4.2.2 Setting guidelines
There are two settings related to the IEC 61850–8–1 protocol:
Operation User can set IEC 61850 communication to Enabled or Disabled.
GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send and received.
4.2.3 Setting parameters
Table 236: IEC61850-8-1 Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
GOOSE Front
OEM311_AB
OEM311_CD
- - OEM311_AB Port for GOOSE communication
Table 237: GOOSEBINRCV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
1MRK504116-UUS C Section 4
Station communication
811