Figure 329: Protection functions configured in 2 WDG transformer with double
breaker at each winding side
6.2.1.3 Description of configuration B40
This configuration gives complete protection for a three winding transformer with two
breakers on each winding as used on ring bus, or breaker and ½ arrangements. The
tripping is three pole. A provision for Synch check is also provided.
The main protection for the transformer is differential protection. Both the traditional
ampere turn differential, and Kirchoff’s Law based differential protection are available.
Complementing the transformer differential protection is 87N, restricted ground fault
protection, and 87B, bus bar protection.