Table 214: General settings parameters for the Measurement function
Setting Short description Selected
value
Comment
Operation Operation Off/On On Function must be
On
PowAmpFact Amplitude factor to scale power
calculations
1.000 Typically no scaling is required
PowAngComp Angle compensation for phase
shift between measured I & V
0.0 Typically no angle compensation is
required. As well here required
direction of P & Q measurement is
towards protected object (as per IED
internal default direction)
Mode Selection of measured current
and voltage
Arone Generator VTs are connected
between phases (V-connected)
k Low pass filter coefficient for
power measurement, V and I
0.00 Typically no additional filtering is
required
VGenZeroDb Zero point clamping in % of
Vbase
25% Set minimum voltage level to 25%
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%
VBase Base setting for voltage level in
kV
15,65 Set generator rated phase-to-phase
voltage
IBase Base setting for current level in A 3690 Set generator rated current
3.15.1.4 Setting parameters
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in PCM600.
Table 215: CVMMXN Non group settings (basic)
Name
Values (Range) Unit Step Default Description
SLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBase
SLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBase
SMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBase
SMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
SRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
PMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
PMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
PRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
QMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
QMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
Table continues on next page
1MRK504116-UUS C Section 3
IED application
761
Application manual