230kV Busbar
300/5
4000/5
100 MVA
G
P Q
100 MVA
15.65kV
ANSI09000041-1-en.vsd
15/0.12kV
V
AB ,
V
BC
,
IED
ANSI09000041 V1 EN
Figure 308: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 308, it is
necessary to do the following:
1. Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef(see section 
 "Analog inputs") using PCM600 for analog input
channels
2. Connect, in PCM600, measurement function to the generator CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
Section 3 1MRK504116-UUS C
IED application
760
Application manual