The required time delays for different distance-protection zones are independent of
each other. Distance protection zone1 can also have a time delay, if so required for
selectivity reasons. One can set the time delays for all zones (basic and optional) in a
range of 0 to 60 seconds. The tripping function of each particular zone can be inhibited
by setting the corresponding Operation parameter to Disabled. Different time delays
are possible for the ph-E (tPG) and for the ph-ph (tPP) measuring loops in each
distance protection zone separately, to further increase the total flexibility of a distance
protection.
3.6.2.3 Setting parameters
Settings for ZMCPDIS (21) are valid for zone 1, while settings for
ZMCAPDIS (21) are valid for zone 2 - 5
Table 53: ZMCPDIS (21) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Disable/Enable Operation
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
VBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Disabled
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
OperationPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Phase loops
X1FwPP 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-Ph,
forward
R1PP 0.01 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-Ph
RFltFwdPP 0.10 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
X1RvPP 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-Ph,
reverse
RFltRevPP 0.10 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, reverse
Timer tPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Zone
timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPG Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Ground loops
X1FwPG 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-G,
forward
Table continues on next page
Section 3 1MRK504116-UUS C
IED application
248
Application manual