3.15.4.2 Setting guidelines
The pulse time t is the only setting for the Logical signal status report (BINSTATREP).
Each output can be set or reset individually, but the pulse time will be the same for all
outputs in the entire BINSTATREP function.
3.15.4.3 Setting parameters
Table 228: BINSTATREP Non group settings (basic)
Name Values (Range) Unit Step Default Description
t 0.000 - 60000.000 s 0.001 10.000 Time delay of function
3.15.5 Measured value expander block RANGE_XP
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block RANGE_XP - -
3.15.5.1 Application
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI and
VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits, that is low-low limit, low limit, high limit and high-
high limit. The measure value expander block ( RANGE_XP) has been introduced to
be able to translate the integer output signal from the measuring functions to 5 binary
signals, that is below low-low limit, below low limit, normal, above high-high limit or
above high limit. The output signals can be used as conditions in the configurable logic.
3.15.5.2 Setting guidelines
There are no settable parameters for the measured value expander block function.
3.15.6 Disturbance report DRPRDRE
Section 3 1MRK504116-UUS C
IED application