Remember that values of parameters set elsewhere are linked to the information on a
report. Such parameters are, for example, station and object identifiers, CT and VT ratios.
3.15.6.3 Setting parameters
Table 229: DRPRDRE Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Enable/Disable
PreFaultRecT 0.05 - 9.90 s 0.01 0.10 Pre-fault recording time
PostFaultRecT 0.1 - 10.0 s 0.1 0.5 Post-fault recording time
TimeLimit 0.5 - 10.0 s 0.1 1.0 Fault recording time limit
PostRetrig Disabled
Enabled
- - Disabled Post-fault retrig enabled (On) or not (Off)
ZeroAngleRef 1 - 30 Ch 1 1 Reference channel (voltage), phasors,
frequency measurement
OpModeTest Disabled
Enabled
- - Disabled Operation mode during test mode
Table 230: A1RADR Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation01 Disabled
Enabled
- - Disabled Operation On/Off
NomValue01 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 1
UnderTrigOp01 Disabled
Enabled
- - Disabled Use under level trig for analog cha 1 (on) or
not (off)
UnderTrigLe01 0 - 200 % 1 50 Under trigger level for analog cha 1 in % of
signal
OverTrigOp01 Disabled
Enabled
- - Disabled Use over level trig for analog cha 1 (on) or
not (off)
OverTrigLe01 0 - 5000 % 1 200 Over trigger level for analog cha 1 in % of signal
Operation02 Disabled
Enabled
- - Disabled Operation On/Off
NomValue02 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 2
UnderTrigOp02 Disabled
Enabled
- - Disabled Use under level trig for analog cha 2 (on) or
not (off)
UnderTrigLe02 0 - 200 % 1 50 Under trigger level for analog cha 2 in % of
signal
OverTrigOp02 Disabled
Enabled
- - Disabled Use over level trig for analog cha 2 (on) or
not (off)
OverTrigLe02 0 - 5000 % 1 200 Over trigger level for analog cha 2 in % of signal
Table continues on next page
Section 3 1MRK504116-UUS C
IED application
788
Application manual