ABB RET670 - Instantaneous Residual Overcurrent Protection EFPIOC (50 N)

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Values (Range) Unit Step Default Description
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer programmable
curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer programmable
curve for step 3
HarmRestrain3 Disabled
Enabled
- - Disabled Enable block of step3 from harmonic restrain
ResetTypeCrv4 Instantaneous
IEC Reset
ANSI reset
- - Instantaneous Selection of reset curve type for step 4
tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC Definite Time
curve step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer programmable
curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer programmable
curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer programmable
curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer programmable
curve for step 4
HarmRestrain4 Disabled
Enabled
- - Disabled Enable block of step 4 from harmonic restrain
Table 91: OC4PTOC (51_67) Non group settings (basic)
Name
Values (Range) Unit Step Default Description
MeasType DFT
RMS
- - DFT Selection between DFT and RMS
measurement
3.7.3 Instantaneous residual overcurrent protection EFPIOC (50N)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous residual overcurrent
protection
EFPIOC
IN>>
IEF V1 EN
50N
Section 3 1MRK504116-UUS C
IED application
418
Application manual