Name Values (Range) Unit Step Default Description
V2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
V2HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
V2HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
V2LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
V2LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
V2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
3.15.2 Event counter CNTGGIO
3.15.2.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event counter CNTGGIO
S00946 V1 EN
-
3.15.2.2 Application
Event counter (CNTGGIO) has six counters which are used for storing the number of
times each counter has been activated. CNTGGIO can be used to count how many
times a specific function, for example the tripping logic, has issued a trip signal. All six
counters have a common blocking and resetting feature.
3.15.2.3 Setting parameters
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600)
3.15.3 Event function EVENT
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function EVENT
S00946 V1 EN
-
1MRK504116-UUS C Section 3
IED application
775
Application manual